SW/ST

Improved acoustic performance
Euroclass A1 Fire classification
Robust high density
Stonewool
SW/ST
Unilin’s range of non-combustible, Euroclass ‘A1’ Stonewool Insulation provides surety when the highest fire performance is required. Stonewool Soffit provides effective fire performance in structural ceiling applications in both residential and commercial buildings.
Our Stonewool Insulation provides a robust, uniform, high density insulation solution suitable for mechanically fixing to concrete substrates.
Benefits
-
Euroclass A1 Fire Classification
-
Robust high density
-
Improved acoustic performance

Specification Clause
The soffit insulation shall be Unilin Insulation Stonewool _ _ mm manufactured to BS EN 13162. The Unilin Insulation Stonewool _ mm with a Declared Lambda value of 0.036 W/mK to achieve a U-Value of _ _W/m2K for the ceiling element. To be installed in accordance with instructions issued by Unilin Insulation.
Resistance ‘R’ Values
The resistance value of any thickness of Unilin insulation can be ascertained by simply dividing the thickness of the material (in metres) by its declared lambda value, for example: Lambda 0.036 W/mK and thickness 100mm -> 0.100/ 0.036 -> R-Value = 2.75. In accordance with EN 13162 R-Values should be rounded down to the nearest 0.05 (m2K/W).
Find out more about SW/ST, Contact Us 046 906 6050
Installation Guidelines
1. Stonewool Soffit can be fixed directly to the concrete slab, to provide an even surface. The rigid product is convenient to handle and allows for fast and easy fixing.
2. Using Stonewool Soffit on soffit areas, whether new build or refurbishment situations, provides the most efficient fire performance. The product achieves a thermal conductivity of 0.036 W/mK and has a Euroclass A1 fire classification.
3. Where applicable, ensure cavity wall insulation has continued past the soffit insulation to reduce Thermal Bridging.
4. Install Stonewool Soffit onto the substrate ensuring all joints are supported. The boards should be tightly butt jointed, laid staggered in a break bonded pattern and fitted tightly at edges and around any service penetrations. Any gaps or service penetrations should be addressed with propriety fillers and components in accordance with fire engineer specifications.
5. Fix Stonewool Soffit to substrate with approved fixings*, ensuring the fixings penetrate the substrate by a minimum of 40mm. Generally, 6 fixings (min shank diameter of 5.2mm) per board are required. Fixings should have a head diameter of at least 50mm. Distribute fixings evenly across the board, at a maximum of 300mm across and 400mm along. It is recommended to seek advice from the fixing manufacturer for specific guidance
6. For advice on soffit fixings, contact the system specifier, ensuring all fixings are accounted for when modelling thermal performance
7. Suitable Board Fixing ManufacturersHilti/EJOT/Fischer
*Fixing type and specification should be verified by the fixing manufacturers design, to take account of topographical and fire considerations. Account should be taken of any Thermal Bridging through the fixings as should the effect of any supporting beams. Fixing manufacturers: Ejot or Fischer